{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Honeywell Honeywell C60VR40040 max pressure switch C60VR40040

SKU C60VR40040 Brand Honeywell

Photos

Key specifications

Setting range5–40 mbar
Body materialaluminum
Electrical connectionDIN plug
Switching element1x SPDT
Setting range0.005–0.04 bar
Component typepressure switch
Ambient temperature, max70 °C
Ambient temperature, min-10 °C
all specifications (8) ↓
88.65 EUR
80.59EUR
in stock · 21

incl. 21% VAT · 66.60 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Honeywell C60VR40040 is a maximum gas pressure switch with a setting range of 5 to 40 mbar (0.005–0.04 bar). It is designed for direct mounting on VQ400 dual valves and VRB00/VR400/V4730 combination gas valves. The switch monitors upstream gas pressure and prevents burner start or forces shutdown if pressure exceeds the preset threshold. It features an aluminum body, DIN plug electrical connection, and a 1x SPDT switching element. The ambient temperature range is -10 to 70 °C.

Further details

Protection ClassIP00 (IP54 with DIN plug installed)

Choosing and fitting

When selecting a replacement pressure switch of this type, verify the pressure range, connection type (flanged or threaded), and electrical contact rating. Ensure the mounting configuration matches the valve body and that the impulse line is clear. Confirm the switching element type (e.g., SPDT) and the ambient temperature limits suit the installation environment.

Signs of failure

Typical failures include a torn diaphragm, drifted setpoint due to wear or contamination, and corrosion of the adjusting spring or microswitch. These may cause burner lockouts during start sequence or after stable operation. Check the switch by applying pressure with a hand pump and comparing the switching point with a manometer.

All specifications

Setting range5–40 mbar
Body materialaluminum
Electrical connectionDIN plug
Switching element1x SPDT
Setting range0.005–0.04 bar
Component typepressure switch
Ambient temperature, max70 °C
Ambient temperature, min-10 °C

Part numbers

SKUC60VR40040
Additional article534.676.900