Key specifications
| Connection thread | 2 x ¼" NPT (female) |
|---|---|
| Adjusting range | 12–60 mbar |
| Switching function | activates on pressure rise |
| Gold-plated contacts | gold-plated |
| Pilot lamp color | green/red |
| Conduit thread | ½" NPT |
| Certification | UL, FM approved |
| Media compatibility | gas, air, biogas |
| Adjustment method | hand wheel |
| Construction type | differential pressure switch |
| Reset type | automatic (auto reset) |
| Country of origin | Germany |
221.62 EUR
201.47EUR
in stock · 1
incl. 21% VAT · 166.50 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
Differential pressure switch for gas, air, and biogas, model DG 150TG-22K2. The switching point is set with a hand wheel over a range of 12–60 mbar; the device resets automatically and the contact activates on pressure rise. It has gold-plated contacts and a green/red pilot lamp. Process connections are two ¼" NPT female ports; the electrical conduit is ½" NPT. The switch carries UL and FM approval and is manufactured in Germany.
Further details
| Application | industrial gas burners and boilers; gas and air supply systems; fan and differential pressure monitoring; heat generators, dryers and gas-fired process lines |
|---|
Choosing and fitting
Pressure switches of this type are selected by the controlled medium, the adjustable switching range, the differential between make and break points, the process connection size, and the contact rating for the burner control circuit. The impulse line is typically connected downstream of the gas filter. Parts of this kind may be mounted directly on the gas train or on a bracket with a flexible impulse tube. Before ordering, measure the setpoint and the differential on the existing unit and verify the electrical connection thread size.
Signs of failure
Common failures are a torn diaphragm caused by pressure spikes, a blocked impulse tube from debris, or a drifted setpoint due to vibration or age. These appear as repeated burner lockouts that resemble ignition faults. When this happens, check the pressure switch function by verifying the setpoint and ensuring the impulse line is clear before replacing the switch.
All specifications
| Connection thread | 2 x ¼" NPT (female) |
|---|---|
| Adjusting range | 12–60 mbar |
| Switching function | activates on pressure rise |
| Gold-plated contacts | gold-plated |
| Pilot lamp color | green/red |
| Conduit thread | ½" NPT |
| Certification | UL, FM approved |
| Media compatibility | gas, air, biogas |
| Adjustment method | hand wheel |
| Construction type | differential pressure switch |
| Reset type | automatic (auto reset) |
| Country of origin | Germany |
Part numbers
| SKU | 84447833 |
|---|---|
| Additional article | 624.214.267 |
| Model | DG 150TG-22K2 |