Kromschroder Gas pressure switch DG 150UG-6 84447521

SKU 84447521 Model DG 150UG-6 Brand Kromschroder

Photos

no photo yet

Key specifications

Setting range30–150 mbar
Functiongas pressure control
Adjustment methodhandwheel
Media compatibilitygas, air, biogas
Gold-plated contactsgold contacts
CertificationCE, EAC, RoHS
Electrical connection4-pin connector with socket
all specifications (7) ↓
235.98 EUR
214.53EUR
in stock · 2

incl. 21% VAT · 177.30 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

This is an industrial gas pressure switch from Kromschroder, model DG 150UG-6, SKU 84447521, in the pressure switch category. It monitors gas, air, and biogas pressure with an adjustable setpoint range of 30–150 mbar. The switching point is set via a handwheel, and electrical connection is made through a 4-pin connector with socket. It features gold-plated contacts for consistent low-level switching. The device carries CE, EAC, and RoHS certifications.

Further details

Applicationgas installations, burner systems, boilers, ventilation and other process systems

Choosing and fitting

Parts of this type are selected by the medium (gas, air or biogas), the required switching range and differential between trip and reset, the connection thread or hose spigot size, and the contact rating to suit the burner control. An impulse line is normally connected to the process pressure, and the unit should be mounted with the diaphragm in the specified orientation. Before ordering, compare the model's marked range and the actual setpoint needed, and confirm the safety approval class (for example EN 1854) is accepted in your jurisdiction. On installation, ensure the impulse line is clean, and recheck the setpoint with a manometer per the commissioning sheet.

Signs of failure

Common failure modes include a torn diaphragm, a blocked impulse tube, or a drifted setpoint. The burner then locks out or fails to start, often misdiagnosed as an ignition fault. Check the impulse line for blockage, inspect the diaphragm, and verify the setpoint against a manometer.

All specifications

Setting range30–150 mbar
Functiongas pressure control
Adjustment methodhandwheel
Media compatibilitygas, air, biogas
Gold-plated contactsgold contacts
CertificationCE, EAC, RoHS
Electrical connection4-pin connector with socket

Part numbers

SKU84447521
Additional article624.214.264
ModelDG 150UG-6