Kromschroder Gas pressure switch DG150U-5 84447506
SKU 84447506
Model DG150U-5
Brand Kromschroder
Photos
Key specifications
| Setting range | 30–150 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| EN 1854 | 2010 |
| Electrical connection | 4-pin plug, without socket |
| Line entrance thread | M16 x 1.5 |
| Safety class | 1 |
| Diaphragm material | NBR |
| Lower housing material | AlSi 12 |
| Silicone-free | yes |
| Low gas release | yes |
| Standards | EN 13611:2015+AC:2016, EN 1854:2010 |
| Certification | CE-0085AP0467 |
| Screw terminals | yes |
| Notified body | 85 |
232.55 EUR
211.41EUR
in stock · 5
incl. 21% VAT · 174.72 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder DG150U-5 gas pressure switch monitors gas or air pressure changes, both increasing and decreasing. It has an adjustable pressure range of 30–150 mbar and is suitable for natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1% by vol. H2S), and air. The switch features a glass fibre reinforced PBT plastic housing with a lower housing section of AlSi 12, and a silicone-free NBR diaphragm. It operates with a 4-pin plug (without socket) and screw terminals, with an M16 x 1.5 line entrance. The device meets EN 13611:2015+AC:2016 and EN 1854:2010 standards, holds CE-0085AP0467 certification, and is safety class 1.
Further details
| Aging effect | long-term use in upper ambient temperature range accelerates ageing of elastomer materials and reduces service life |
|---|---|
| EN 13611 | 2015+AC:2016 |
| Function | monitor changes in gas or air pressure, whether increasing or decreasing |
| Maintenance interval | annually, or every six months if operates with biogas |
| Post-maintenance leak check | check for any leaks in the system |
| Pressure Type | rising positive pressure (gas/air), negative pressure (air), differential pressure (air-air) |
| Production surveillance | subject to surveillance procedures as per directive 2009/142/EC, annex II, and regulation (EU) 2016/426, annex III, paragraph 3 |
Choosing and fitting
When selecting a replacement pressure switch of this type, verify the pressure range, electrical connection (e.g., plug type and terminal configuration), and process connection thread size. Ensure the switch is suitable for the gas or air type and that the ambient and medium temperatures are within the specified limits. Check the enclosure rating and safety class to match the application requirements. Mounting must align with the original orientation and line entrance position.
Signs of failure
Common failures include diaphragm rupture or leakage, leading to loss of pressure sensing and incorrect switching. Electrical contact issues may cause intermittent or no signal. Symptoms on equipment include burner lockout, failure to start, or erratic pressure control. Regular functional checks, especially for decreasing pressure, are recommended to detect faults early.
All specifications
| Setting range | 30–150 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| EN 1854 | 2010 |
| Electrical connection | 4-pin plug, without socket |
| Line entrance thread | M16 x 1.5 |
| Safety class | 1 |
| Diaphragm material | NBR |
| Lower housing material | AlSi 12 |
| Silicone-free | yes |
| Low gas release | yes |
| Standards | EN 13611:2015+AC:2016, EN 1854:2010 |
| Certification | CE-0085AP0467 |
| Screw terminals | yes |
| Notified body | 85 |
Part numbers
| SKU | 84447506 |
|---|---|
| Additional article | 624.214.191 |
| Model | DG150U-5 |