Kromschroder Gas pressure switch DG50H-3T 84447624
SKU 84447624
Model DG50H-3T
Brand Kromschroder
Photos
Key specifications
| Setting range | 2.5–50 mbar |
|---|---|
| Connection thread | M16 x 1.5 |
| Body material | glass fibre reinforced PBT plastic |
| Adjusting range | 2.5–50 mbar |
| Maximum medium and ambient temperatures | -15–60 °C |
| Storage temperature | -20–40 °C |
| Safety class | 1 |
| Line diameter | 0.5–1.8 mm |
| Weight | 321 g |
| Diaphragm material | NBR |
| Lower housing material | AlSi 12 |
| Silicone-free | yes |
| Low gas release | yes |
| Line entrance thread | M16 x 1.5 |
| Construction type | diaphragm pressure switch |
283.64 EUR
257.85EUR
in stock · 2
incl. 21% VAT · 213.10 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder DG50H-3T is a diaphragm pressure switch designed to monitor gas or air pressure in burner and boiler systems. It has an adjusting range of 2.5 to 50 mbar and is suitable for use with natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1% by vol. H2S), and air. The switch operates within a maximum medium and ambient temperature range of -15 to 60 °C and a storage temperature of -20 to 40 °C. It features a glass fibre reinforced PBT plastic housing with low gas release, an NBR diaphragm, and an AlSi 12 lower housing section. The device is silicone-free, has safety class 1, and is rated IP 54. It weighs 321 g and has a line diameter of 0.5 to 1.8 mm, with a connection thread of M16 x 1.5.
Further details
| Diaphragm | NBR |
|---|---|
| Electrical Connection | screw terminals and M16 cable gland |
| Enclosure | IP 54 or IP 65 |
| Gas type | natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1 %-by-vol. H2S) and air |
| Housing | glass fibre reinforced PBT plastic with low gas release |
| Line entrance | M16 x 1.5, clamping range: diameters of 4 to 10 mm |
| Lower housing section | AlSi 12 |
| Type of connection | screw terminals |
Choosing and fitting
When selecting a pressure switch of this type, ensure the adjusting range, connection thread, and electrical ratings match the system requirements. The switch is typically installed via the M16 x 1.5 thread and connected using screw terminals. Verify the line diameter (0.5–1.8 mm) and cable gland clamping range (4–10 mm) to ensure proper sealing. The switch may be mounted in any orientation, but the diaphragm must be positioned correctly to sense pressure changes.
Signs of failure
Common failure modes for diaphragm pressure switches include diaphragm rupture or leakage, which can cause the switch to fail to actuate or to actuate at incorrect pressures. Symptoms on the equipment may include burner lockout, erratic operation, or failure to start. Check for gas leaks, inspect the diaphragm for damage, and verify the switch's setpoint against a manometer.
Fits equipment
IP 54
All specifications
| Setting range | 2.5–50 mbar |
|---|---|
| Connection thread | M16 x 1.5 |
| Body material | glass fibre reinforced PBT plastic |
| Adjusting range | 2.5–50 mbar |
| Maximum medium and ambient temperatures | -15–60 °C |
| Storage temperature | -20–40 °C |
| Safety class | 1 |
| Line diameter | 0.5–1.8 mm |
| Weight | 321 g |
| Diaphragm material | NBR |
| Lower housing material | AlSi 12 |
| Silicone-free | yes |
| Low gas release | yes |
| Line entrance thread | M16 x 1.5 |
| Construction type | diaphragm pressure switch |
Part numbers
| SKU | 84447624 |
|---|---|
| Additional article | 624.214.223 |
| Model | DG50H-3T |