{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Pressure switch for gas DG50U-3A 84447359

SKU 84447359 Model DG50U-3A Brand Kromschroder

Photos

Key specifications

Setting range2.5–50 mbar
Body materialglass fibre reinforced PBT plastic
Line diameter0.5–1.8 mm
Screw terminalsyes
Silicone-freeyes
Low gas releaseyes
Diaphragm systemdiaphragm pressure switch
Switching with rising pressureyes
External adjustmentyes
Electrical connectionscrew terminals
Trigger level adjustmenthandwheel
Pressure typedifferential pressure switch
Monitoring pressure changesyes
Gas sensoryes
Switching contactmicroswitch with switching contact
Diaphragm materialNBR
Lower housing materialAlSi 12
Safety class1
Line entrance threadM16 x 1.5
all specifications (19) ↓
224.04 EUR
203.67EUR
in stock · 1

incl. 21% VAT · 168.32 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DG50U-3A pressure switch (SKU 84447359) is a diaphragm-type differential pressure switch designed to monitor pressure changes in gases or air. It switches with rising positive pressure and features a microswitch with a switching contact. The trigger level is adjustable externally via a handwheel, and the pressure range is 2.5–50 mbar. The housing is made of glass fibre reinforced PBT plastic with low gas release, and the diaphragm is NBR. It is silicone-free and has screw terminals for electrical connection, with a line entrance thread of M16 x 1.5.

Further details

Functionmonitor pressure changes in gases or air, regardless of increasing or decreasing
Long-term use upper tempaccelerates ageing of elastomer materials and reduces service life
Microswitch activationwhen set pressure reached, microswitch with switching contact is switched on
Response to pressure deviationsrespond to any pressure deviations from the setpoint

Choosing and fitting

When selecting a pressure switch of this type, ensure the pressure range, switching function (rising or falling), and electrical connection match the application. Check the line diameter (0.5–1.8 mm) and line entrance thread (M16 x 1.5) for compatibility with existing wiring and conduit. The switch may be used for positive, negative, or differential pressure monitoring, so verify the pressure type required. Installation involves connecting the pressure lines and wiring the screw terminals, then adjusting the setpoint with the handwheel.

Signs of failure

Common failure modes for diaphragm pressure switches include diaphragm rupture or leakage, which can cause the switch to fail to actuate or to actuate at incorrect pressures. Symptoms may include burner lockouts, erratic operation, or failure to detect pressure changes. Check for physical damage to the housing, verify the diaphragm integrity, and test the switch operation against a known pressure source.

All specifications

Setting range2.5–50 mbar
Body materialglass fibre reinforced PBT plastic
Line diameter0.5–1.8 mm
Screw terminalsyes
Silicone-freeyes
Low gas releaseyes
Diaphragm systemdiaphragm pressure switch
Switching with rising pressureyes
External adjustmentyes
Electrical connectionscrew terminals
Trigger level adjustmenthandwheel
Pressure typedifferential pressure switch
Monitoring pressure changesyes
Gas sensoryes
Switching contactmicroswitch with switching contact
Diaphragm materialNBR
Lower housing materialAlSi 12
Safety class1
Line entrance threadM16 x 1.5

Part numbers

SKU84447359
Additional article624.214.198
ModelDG50U-3A