Kromschroder Pressure switch for gas DG50U-3A 84447359
SKU 84447359
Model DG50U-3A
Brand Kromschroder
Photos
Key specifications
| Setting range | 2.5–50 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| Line diameter | 0.5–1.8 mm |
| Screw terminals | yes |
| Silicone-free | yes |
| Low gas release | yes |
| Diaphragm system | diaphragm pressure switch |
| Switching with rising pressure | yes |
| External adjustment | yes |
| Electrical connection | screw terminals |
| Trigger level adjustment | handwheel |
| Pressure type | differential pressure switch |
| Monitoring pressure changes | yes |
| Gas sensor | yes |
| Switching contact | microswitch with switching contact |
| Diaphragm material | NBR |
| Lower housing material | AlSi 12 |
| Safety class | 1 |
| Line entrance thread | M16 x 1.5 |
224.04 EUR
203.67EUR
in stock · 1
incl. 21% VAT · 168.32 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder DG50U-3A pressure switch (SKU 84447359) is a diaphragm-type differential pressure switch designed to monitor pressure changes in gases or air. It switches with rising positive pressure and features a microswitch with a switching contact. The trigger level is adjustable externally via a handwheel, and the pressure range is 2.5–50 mbar. The housing is made of glass fibre reinforced PBT plastic with low gas release, and the diaphragm is NBR. It is silicone-free and has screw terminals for electrical connection, with a line entrance thread of M16 x 1.5.
Further details
| Function | monitor pressure changes in gases or air, regardless of increasing or decreasing |
|---|---|
| Long-term use upper temp | accelerates ageing of elastomer materials and reduces service life |
| Microswitch activation | when set pressure reached, microswitch with switching contact is switched on |
| Response to pressure deviations | respond to any pressure deviations from the setpoint |
Choosing and fitting
When selecting a pressure switch of this type, ensure the pressure range, switching function (rising or falling), and electrical connection match the application. Check the line diameter (0.5–1.8 mm) and line entrance thread (M16 x 1.5) for compatibility with existing wiring and conduit. The switch may be used for positive, negative, or differential pressure monitoring, so verify the pressure type required. Installation involves connecting the pressure lines and wiring the screw terminals, then adjusting the setpoint with the handwheel.
Signs of failure
Common failure modes for diaphragm pressure switches include diaphragm rupture or leakage, which can cause the switch to fail to actuate or to actuate at incorrect pressures. Symptoms may include burner lockouts, erratic operation, or failure to detect pressure changes. Check for physical damage to the housing, verify the diaphragm integrity, and test the switch operation against a known pressure source.
All specifications
| Setting range | 2.5–50 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| Line diameter | 0.5–1.8 mm |
| Screw terminals | yes |
| Silicone-free | yes |
| Low gas release | yes |
| Diaphragm system | diaphragm pressure switch |
| Switching with rising pressure | yes |
| External adjustment | yes |
| Electrical connection | screw terminals |
| Trigger level adjustment | handwheel |
| Pressure type | differential pressure switch |
| Monitoring pressure changes | yes |
| Gas sensor | yes |
| Switching contact | microswitch with switching contact |
| Diaphragm material | NBR |
| Lower housing material | AlSi 12 |
| Safety class | 1 |
| Line entrance thread | M16 x 1.5 |
Part numbers
| SKU | 84447359 |
|---|---|
| Additional article | 624.214.198 |
| Model | DG50U-3A |