Key specifications

Setting range2.5–50 mbar
Connection threadM16 x 1.5
Protection class (IP)IP65
Body materialglass fibre reinforced PBT plastic
Sensing elementNBR diaphragm
Operating principlemechanical pressure switch
Safety class1
Diaphragm materialNBR
Catalogue article numbers84447021, 624.214.094
Ingress protectionIP65
Component typepressure switch
Lower housing materialAlSi12
Silicone-freeyes
Low gas releaseyes
Pilot lamp colorgreen/red
Conduit threadM16 x 1.5
Gold-plated contactsyes
Line entrance threadM16 x 1.5
Pilot lamp voltage24 V AC/DC
Screw terminalsyes
SKU (English)84447021, 624.214.094
Switching with rising pressureyes
Post-maintenance leak checkyes
Diaphragm pressure switchyes
Construction typediaphragm pressure switch
all specifications (25) ↓
292.36 EUR
265.78EUR
in stock · 4

incl. 21% VAT · 219.65 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DG50UG-4K2 is a diaphragm pressure switch with a pressure range of 2.5–50 mbar. It features a glass fibre reinforced PBT plastic housing with a lower housing section made of AlSi12, and an NBR diaphragm. The switch is silicone-free, has gold-plated contacts, and includes a green/red pilot lamp for 24 V AC/DC. It is rated IP65 and has a safety class of 1, with a connection thread of M16 x 1.5. This device is designed for monitoring pressure in gas or air environments, suitable for media such as natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1 %-by-vol. H2S), and air.

Further details

Electrical Connectionscrew terminals and M16 cable gland
Functionmonitoring pressure fluctuations in gas or air
Switching Functionswitches with rising positive pressure (gas/air), negative pressure (air), differential pressure (air-air)

Choosing and fitting

When selecting a pressure switch of this type, ensure the pressure range, connection thread, and electrical specifications match the system requirements. The switch must be compatible with the medium and ambient temperature range. Installation involves connecting the pressure line to the appropriate port and wiring the electrical connections via screw terminals. Verify the switching function with rising pressure and perform a leak check after maintenance.

Signs of failure

Common failures include diaphragm rupture or leakage, leading to loss of pressure sensing and incorrect switching. Electrical contact issues may cause intermittent operation or failure to signal. Check for physical damage, contamination, or corrosion on contacts. Verify the switch responds correctly to pressure changes and that the pilot lamp indicates status properly.

All specifications

Setting range2.5–50 mbar
Connection threadM16 x 1.5
Protection class (IP)IP65
Body materialglass fibre reinforced PBT plastic
Sensing elementNBR diaphragm
Operating principlemechanical pressure switch
Safety class1
Diaphragm materialNBR
Catalogue article numbers84447021, 624.214.094
Ingress protectionIP65
Component typepressure switch
Lower housing materialAlSi12
Silicone-freeyes
Low gas releaseyes
Pilot lamp colorgreen/red
Conduit threadM16 x 1.5
Gold-plated contactsyes
Line entrance threadM16 x 1.5
Pilot lamp voltage24 V AC/DC
Screw terminalsyes
SKU (English)84447021, 624.214.094
Switching with rising pressureyes
Post-maintenance leak checkyes
Diaphragm pressure switchyes
Construction typediaphragm pressure switch

Part numbers

SKU84447021
Additional article624.214.094
ModelDG50UG-4K2