Kromschroder Gas pressure switch DG50UG-9K2 84447022
SKU 84447022
Model DG50UG-9K2
Brand Kromschroder
Photos
no photo yet
Key specifications
| Setting range | 2.5–50 mbar |
|---|---|
| Connection thread | M16 x 1.5 |
| Protection class (IP) | IP65 |
| Body material | glass fibre reinforced PBT plastic |
| EN 1854 | 2010 |
| Sensing element | diaphragm |
| Electrical connection | 4-pin plug, with socket |
| Safety class | 1 |
| Diaphragm material | NBR |
| Ingress protection | IP65 |
| Component type | pressure switch |
| Lower housing material | AlSi 12 |
| Silicone-free | yes |
| Low gas release | yes |
| Line entrance thread | M16 x 1.5 |
| Pilot lamp voltage | 24 V AC/DC |
| Screw terminals | yes |
| Switching with rising pressure | yes |
| Diaphragm pressure switch | yes |
| Construction type | diaphragm pressure switch |
| Supply voltage | 24 V |
288.96 EUR
262.69EUR
in stock · 2
incl. 21% VAT · 217.10 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder DG50UG-9K2 (SKU 84447022) is a diaphragm pressure switch designed to monitor pressure fluctuations in gas or air environments. It has an adjustable pressure range of 2.5 to 50 mbar and operates with a supply voltage of 24 V AC/DC. The switch features a glass fibre reinforced PBT plastic housing with a lower housing section made of AlSi 12, and a diaphragm made of NBR. It is silicone-free, has low gas release, and is rated IP65 for ingress protection. The electrical connection is via a 4-pin plug with socket and screw terminals, and it includes a pilot lamp for 24 V AC/DC. This model complies with EN 1854:2010 and safety class 1.
Further details
| EN 13611 | 2015+AC:2016 |
|---|
Choosing and fitting
When selecting a replacement pressure switch of this type, ensure the pressure range, connection thread (M16 x 1.5), and electrical connection (voltage and plug type) match the original. The switch is designed for rising pressure and can be used for gas or air applications. Verify the medium compatibility and temperature range, and check the ingress protection rating required for the installation environment. Mounting should follow the manufacturer's guidelines, ensuring proper sealing and electrical connections.
Signs of failure
Common failures of diaphragm pressure switches include diaphragm rupture or leakage, leading to loss of pressure sensing or false triggering. Electrical contact issues may cause intermittent operation or failure to switch. Symptoms on equipment include burner lockouts, erratic pressure readings, or failure to start. Check for physical damage, contamination, and verify the switch operation with a manometer and multimeter.
All specifications
| Setting range | 2.5–50 mbar |
|---|---|
| Connection thread | M16 x 1.5 |
| Protection class (IP) | IP65 |
| Body material | glass fibre reinforced PBT plastic |
| EN 1854 | 2010 |
| Sensing element | diaphragm |
| Electrical connection | 4-pin plug, with socket |
| Safety class | 1 |
| Diaphragm material | NBR |
| Ingress protection | IP65 |
| Component type | pressure switch |
| Lower housing material | AlSi 12 |
| Silicone-free | yes |
| Low gas release | yes |
| Line entrance thread | M16 x 1.5 |
| Pilot lamp voltage | 24 V AC/DC |
| Screw terminals | yes |
| Switching with rising pressure | yes |
| Diaphragm pressure switch | yes |
| Construction type | diaphragm pressure switch |
| Supply voltage | 24 V |
Part numbers
| SKU | 84447022 |
|---|---|
| Additional article | 624.214.252 |
| Model | DG50UG-9K2 |