Kromschroder Gas pressure switch DG6U-6 84447251

SKU 84447251 Model DG6U-6 Brand Kromschroder

Photos

Key specifications

Body materialglass fibre reinforced PBT plastic
Adjusting range0.4–6 mbar
Safety class1
Line entrance threadM16 x 1.5
Electrical connection4-pin plug, with socket
Diaphragm materialNBR
Lower housing materialAlSi 12
Silicone-freeyes
Low gas releaseyes
Operating principlediaphragm pressure switch
Construction typediaphragm pressure switch
Sensing elementdiaphragm
Screw terminalsyes
all specifications (13) ↓
259.13 EUR
235.57EUR
in stock · 5

incl. 21% VAT · 194.69 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DG6U-6 gas pressure switch (SKU 84447251) is a diaphragm-type pressure switch designed to monitor pressure changes in gas or air systems. It has an adjusting range of 0.4 to 6 mbar and operates with rising positive pressure (gas/air), negative pressure (air), or differential pressure (air-air). The switch features a silicone-free NBR diaphragm, a glass fibre reinforced PBT plastic housing with low gas release, and a lower housing section made of AlSi 12. It is safety class 1, has a line entrance thread of M16 x 1.5, and connects via a 4-pin plug with socket and screw terminals. The switch is suitable for media such as natural gas, town gas, LPG (gaseous), flue gas, biogas (max. 0.1% by volume H2S), and air.

Further details

Switching With Rising Pressurerising positive pressure (gas/air), negative pressure (air), differential pressure (air-air)

Choosing and fitting

When selecting a replacement pressure switch of this type, ensure the adjusting range, electrical connection (e.g., plug type and terminal configuration), and line entrance thread match the existing installation. The switch must be compatible with the medium and pressure direction (positive, negative, or differential). Mounting involves connecting the pressure lines to the appropriate ports and securing the electrical plug. Verify the enclosure rating and temperature limits for the application environment.

Signs of failure

Common failure modes for diaphragm pressure switches include diaphragm rupture or leakage, which can cause the switch to fail to actuate or to actuate at incorrect pressures. Symptoms may include burner lockout, erratic pressure readings, or the system not responding to pressure changes. Check for visible damage to the diaphragm, leaks at connections, and verify the switch operation against a known pressure source.

All specifications

Body materialglass fibre reinforced PBT plastic
Adjusting range0.4–6 mbar
Safety class1
Line entrance threadM16 x 1.5
Electrical connection4-pin plug, with socket
Diaphragm materialNBR
Lower housing materialAlSi 12
Silicone-freeyes
Low gas releaseyes
Operating principlediaphragm pressure switch
Construction typediaphragm pressure switch
Sensing elementdiaphragm
Screw terminalsyes

Part numbers

SKU84447251
Additional article624.214.125
ModelDG6U-6