{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Gas pressure switch DG6UG-6K2 84447263

SKU 84447263 Model DG6UG-6K2 Brand Kromschroder

Photos

no photo yet

Key specifications

Setting range0.4–6 mbar
Adjusting range0.4–6 mbar
Weight350 g
Electrical connectionvia 4-pin plug, with socket
Component typepressure switch
Designed lifetime10 years
Pilot lamp voltage24 V AC/DC
Durability10 years
StandardsEN 13611:2015+AC:2016 and EN 1854:2010
Tested type sampleyes
EN 18542010
Switching with rising pressureyes
ApprovalsCE-0085AP0466
Safety chain roleessential safety components
Certification bodyCE-0085AP0466
Approval classCE-0085AP0466
Supply voltage24 V
all specifications (17) ↓
259.94 EUR
236.31EUR
in stock · 2

incl. 21% VAT · 195.30 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DG6UG-6K2 (SKU 84447263) is a gas pressure switch designed to regulate positive, negative, or differential air and flue gas pressures. It has an adjusting range of 0.4–6 mbar and switches with rising pressure. The switch operates at a supply voltage of 24 V and features a 4-pin plug with socket for electrical connection, including a green/red pilot lamp for 24 V AC/DC. It weighs 350 g and has a designed lifetime of 10 years. The product complies with EN 13611:2015+AC:2016 and EN 1854:2010 standards and holds approval CE-0085AP0466.

Further details

Replacement Criteriaessential safety components must be replaced
Surveillance Procedureproduction surveillance as per directives 2009/142/ec annex ii and regulation (eu) 2016/426 annex iii

Choosing and fitting

When selecting a pressure switch of this type, ensure the adjusting range and pressure range match the application requirements. The electrical connection must be compatible with the existing wiring, typically via a plug or terminals. Verify the supply voltage and pilot lamp voltage (if applicable) match the system. Mounting orientation and process connection size should be checked against the original part. Always compare the switch's switching function (e.g., rising or falling pressure) with the system's control logic.

Signs of failure

Common failure modes for pressure switches include contact wear, diaphragm rupture, or loss of calibration. Symptoms may include the burner failing to start, intermittent shutdowns, or the system not responding to pressure changes. Check for visible damage, test the switch with a manometer, and verify electrical continuity across contacts. If the switch is part of a safety chain, replace it immediately upon any malfunction.

All specifications

Setting range0.4–6 mbar
Adjusting range0.4–6 mbar
Weight350 g
Electrical connectionvia 4-pin plug, with socket
Component typepressure switch
Designed lifetime10 years
Pilot lamp voltage24 V AC/DC
Durability10 years
StandardsEN 13611:2015+AC:2016 and EN 1854:2010
Tested type sampleyes
EN 18542010
Switching with rising pressureyes
ApprovalsCE-0085AP0466
Safety chain roleessential safety components
Certification bodyCE-0085AP0466
Approval classCE-0085AP0466
Supply voltage24 V

Part numbers

SKU84447263
Additional article624.214.236
ModelDG6UG-6K2