{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Air pressure switch DL10E-1 84444270

SKU 84444270 Model DL10E-1 Brand Kromschroder

Photos

Key specifications

Setting range1–10 mbar
Protection class (IP)II
Body materialglass fibre reinforced PBT plastic
Sensing elementtempered LSR diaphragm
Switching elementmicroswitch
Operating principlemechanical pressure switch
Electrical connectionAMP plugs
Mediumair or flue gas
Weight150 g
Adjusting range1–10 mbar
Safety class2
Cover screw65 Ncm
Diaphragm materialLSR
Component typepressure switch
Low gas releaseyes
Designed lifetime10 years
Diaphragm systemtempered LSR diaphragm
Micro switch standardEN 61058-1
Strain relief torque65 Ncm
StandardsEN 13611, EN 1854
Strain relief facility65 Ncm
Construction typediaphragm pressure switch
Contact rating6(2)A 250V
all specifications (23) ↓
144.52 EUR
131.38EUR
in stock · 3

incl. 21% VAT · 108.58 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DL10E-1 is a mechanical diaphragm pressure switch designed for air or flue gas pressure monitoring in boilers and industrial equipment. It has an adjusting range of 1–10 mbar and features a tempered LSR diaphragm system. The housing is made of glass fibre reinforced PBT plastic with low gas release, and the electrical connection uses AMP plugs. The microswitch complies with EN 61058-1, and the device meets safety class II and standards EN 13611 and EN 1854. It weighs 150 g and has a designed lifetime of 10 years.

Further details

Functionregulates air and flue gas pressures
Gas Typeair or flue gas, no flammable gases, no aggressive gases

Choosing and fitting

When selecting a replacement pressure switch of this type, verify the required pressure range, electrical ratings, and connection type. Ensure the medium (air or flue gas) is compatible and that the switch's safety class and standards meet the application's requirements. Mounting involves connecting the pressure ports and securing the cover screw to the specified torque of 65 Ncm. The electrical connection via AMP plugs must match the existing wiring.

Signs of failure

Common failure modes include diaphragm rupture or leakage, leading to loss of pressure sensing or false switching. This may cause the burner to shut down or fail to start. Check for visible damage to the diaphragm, loose electrical connections, or incorrect pressure settings. If the switch fails to operate within its set range, it may need replacement.

All specifications

Setting range1–10 mbar
Protection class (IP)II
Body materialglass fibre reinforced PBT plastic
Sensing elementtempered LSR diaphragm
Switching elementmicroswitch
Operating principlemechanical pressure switch
Electrical connectionAMP plugs
Mediumair or flue gas
Weight150 g
Adjusting range1–10 mbar
Safety class2
Cover screw65 Ncm
Diaphragm materialLSR
Component typepressure switch
Low gas releaseyes
Designed lifetime10 years
Diaphragm systemtempered LSR diaphragm
Micro switch standardEN 61058-1
Strain relief torque65 Ncm
StandardsEN 13611, EN 1854
Strain relief facility65 Ncm
Construction typediaphragm pressure switch
Contact rating6(2)A 250V

Part numbers

SKU84444270
Additional article624.214.058
ModelDL10E-1