Kromschroder Air pressure switch DL1E-1 84444010

SKU 84444010 Model DL1E-1 Brand Kromschroder

Photos

Key specifications

Setting range0.2–1 mbar
Body materialglass fibre reinforced PBT plastic
Weight200 g
Cover screw50 Ncm
Strain relief facility60 Ncm
Electrical connectionvia amp plugs
Micro switch standardEN 61058-1
Safety classVDE 0106-1
Sensing elementdiaphragm
Diaphragm materialNBR
Low gas releaseyes
Silicone-freeyes
Tested type sampleyes
Production surveillanceyes
Pressure typepositive, negative or differential pressure
all specifications (15) ↓
159.89 EUR
145.35EUR
in stock · 28

incl. 21% VAT · 120.12 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DL1E-1 air pressure switch, SKU 84444010, is a diaphragm-based pressure switch designed to monitor positive, negative, or differential pressure of non-aggressive gases, air, or flue gases. It has an adjustable pressure range of 0.2 to 1 mbar. The switch features a glass fibre reinforced PBT plastic body with low gas release, a NBR diaphragm, and is silicone-free. It weighs 200 g, with cover screw torque of 50 Ncm and strain relief facility torque of 60 Ncm. Electrical connection is via AMP plugs, and the micro switch complies with EN 61058-1, with safety class II per VDE 0106-1. The product is tested type sample and subject to production surveillance.

Further details

Aging effectlong-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life
Gas Typeair or flue gas, no flammable gases, no aggressive gases
Mediumnon-aggressive gases, air or flue gases
Replacement criteriaonce the designed lifetime has been reached, safety-relevant products must be replaced

Choosing and fitting

When selecting a replacement pressure switch of this type, verify the required pressure range, electrical connection type (e.g., AMP plugs), and mounting configuration. Ensure the switch is suitable for the medium (air, flue gas, non-aggressive gases) and that the pressure type (positive, negative, or differential) matches the application. Check the ambient and medium temperature limits and confirm the switch's safety certifications align with the system requirements.

Signs of failure

Common failure modes for diaphragm pressure switches include diaphragm rupture or leakage, leading to loss of pressure sensing and incorrect switching. Symptoms may include burner lockout, failure to start, or erratic operation. Check for physical damage, contamination, or corrosion of the diaphragm and housing, and verify the switch operation by measuring continuity across the micro switch terminals while applying pressure.

All specifications

Setting range0.2–1 mbar
Body materialglass fibre reinforced PBT plastic
Weight200 g
Cover screw50 Ncm
Strain relief facility60 Ncm
Electrical connectionvia amp plugs
Micro switch standardEN 61058-1
Safety classVDE 0106-1
Sensing elementdiaphragm
Diaphragm materialNBR
Low gas releaseyes
Silicone-freeyes
Tested type sampleyes
Production surveillanceyes
Pressure typepositive, negative or differential pressure

Part numbers

SKU84444010
Additional article624.214.062
ModelDL1E-1