{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Air pressure switch DL2E-1 84444150

SKU 84444150 Model DL2E-1 Brand Kromschroder

Photos

Key specifications

Setting range0.2–2 mbar
Body materialglass fibre reinforced PBT plastic
Sensing elementtempered LSR diaphragm
Switching elementmicroswitch
Electrical connectionAMP plugs
Weight0.2 g
Safety classII to VDE 0106-1
Cover screw65 Ncm
Strain relief facility65 Ncm
CE product IDCE-0085AP0466
Pressure typepositive, negative or differential pressure
Diaphragm systemtempered LSR diaphragm system
Low gas releaseyes
Micro switch standardEN 61058-1
Safety standardVDE 0106-1
Tested type sampleyes
Mediumair or flue gas
ApprovalsCE-0085AP0466
Certification bodyCE-0085AP0466
Replacement criteriaReplace after designed lifetime
Safety chain roleSafety-relevant product
all specifications (21) ↓
118.57 EUR
107.79EUR
in stock · 7

incl. 21% VAT · 89.08 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DL2E-1 air pressure switch (SKU 84444150) is a safety-relevant product designed to control positive, negative, or differential air or flue gas pressures. It has a pressure range of 0.2–2 mbar and features a tempered LSR diaphragm system within a glass fibre reinforced PBT plastic housing. The switch uses a microswitch conforming to EN 61058-1 and is safety class II to VDE 0106-1. It is approved under CE-0085AP0466 and is suitable for media such as air or flue gas, with a designed lifetime of 10 years.

Further details

Gas Typeair or flue gas, no flammable gases, no aggressive gases

Choosing and fitting

When selecting a replacement pressure switch of this type, ensure the pressure range, electrical connection (e.g., AMP plugs), and safety approvals match the original. The switch must be compatible with the medium (air or flue gas) and the system's pressure type (positive, negative, or differential). Mounting and electrical connections should be verified against the existing unit, and the cover screw and strain relief torque should be set to the specified value (e.g., 65 Ncm) during installation.

Signs of failure

Common failure modes for such pressure switches include diaphragm rupture or leakage, leading to incorrect pressure sensing or no switching action. This may cause the burner to fail to start, shut down unexpectedly, or operate with improper air/fuel ratios. Check for physical damage, contamination, or loose electrical connections, and verify the switch's operation against the set pressure range.

All specifications

Setting range0.2–2 mbar
Body materialglass fibre reinforced PBT plastic
Sensing elementtempered LSR diaphragm
Switching elementmicroswitch
Electrical connectionAMP plugs
Weight0.2 g
Safety classII to VDE 0106-1
Cover screw65 Ncm
Strain relief facility65 Ncm
CE product IDCE-0085AP0466
Pressure typepositive, negative or differential pressure
Diaphragm systemtempered LSR diaphragm system
Low gas releaseyes
Micro switch standardEN 61058-1
Safety standardVDE 0106-1
Tested type sampleyes
Mediumair or flue gas
ApprovalsCE-0085AP0466
Certification bodyCE-0085AP0466
Replacement criteriaReplace after designed lifetime
Safety chain roleSafety-relevant product

Part numbers

SKU84444150
Additional article624.214.064
ModelDL2E-1
Type designationCE-0085AP0466