Kromschroder Air pressure switch DL2E-1 84444150
SKU 84444150
Model DL2E-1
Brand Kromschroder
Photos
Key specifications
| Setting range | 0.2–2 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| Sensing element | tempered LSR diaphragm |
| Switching element | microswitch |
| Electrical connection | AMP plugs |
| Weight | 0.2 g |
| Safety class | II to VDE 0106-1 |
| Cover screw | 65 Ncm |
| Strain relief facility | 65 Ncm |
| CE product ID | CE-0085AP0466 |
| Pressure type | positive, negative or differential pressure |
| Diaphragm system | tempered LSR diaphragm system |
| Low gas release | yes |
| Micro switch standard | EN 61058-1 |
| Safety standard | VDE 0106-1 |
| Tested type sample | yes |
| Medium | air or flue gas |
| Approvals | CE-0085AP0466 |
| Certification body | CE-0085AP0466 |
| Replacement criteria | Replace after designed lifetime |
| Safety chain role | Safety-relevant product |
118.57 EUR
107.79EUR
in stock · 7
incl. 21% VAT · 89.08 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder DL2E-1 air pressure switch (SKU 84444150) is a safety-relevant product designed to control positive, negative, or differential air or flue gas pressures. It has a pressure range of 0.2–2 mbar and features a tempered LSR diaphragm system within a glass fibre reinforced PBT plastic housing. The switch uses a microswitch conforming to EN 61058-1 and is safety class II to VDE 0106-1. It is approved under CE-0085AP0466 and is suitable for media such as air or flue gas, with a designed lifetime of 10 years.
Further details
| Gas Type | air or flue gas, no flammable gases, no aggressive gases |
|---|
Choosing and fitting
When selecting a replacement pressure switch of this type, ensure the pressure range, electrical connection (e.g., AMP plugs), and safety approvals match the original. The switch must be compatible with the medium (air or flue gas) and the system's pressure type (positive, negative, or differential). Mounting and electrical connections should be verified against the existing unit, and the cover screw and strain relief torque should be set to the specified value (e.g., 65 Ncm) during installation.
Signs of failure
Common failure modes for such pressure switches include diaphragm rupture or leakage, leading to incorrect pressure sensing or no switching action. This may cause the burner to fail to start, shut down unexpectedly, or operate with improper air/fuel ratios. Check for physical damage, contamination, or loose electrical connections, and verify the switch's operation against the set pressure range.
All specifications
| Setting range | 0.2–2 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| Sensing element | tempered LSR diaphragm |
| Switching element | microswitch |
| Electrical connection | AMP plugs |
| Weight | 0.2 g |
| Safety class | II to VDE 0106-1 |
| Cover screw | 65 Ncm |
| Strain relief facility | 65 Ncm |
| CE product ID | CE-0085AP0466 |
| Pressure type | positive, negative or differential pressure |
| Diaphragm system | tempered LSR diaphragm system |
| Low gas release | yes |
| Micro switch standard | EN 61058-1 |
| Safety standard | VDE 0106-1 |
| Tested type sample | yes |
| Medium | air or flue gas |
| Approvals | CE-0085AP0466 |
| Certification body | CE-0085AP0466 |
| Replacement criteria | Replace after designed lifetime |
| Safety chain role | Safety-relevant product |
Part numbers
| SKU | 84444150 |
|---|---|
| Additional article | 624.214.064 |
| Model | DL2E-1 |
| Type designation | CE-0085AP0466 |