Key specifications

Setting range0.45–2 mbar
Body materialglass fibre reinforced PBT plastic
Sensing elementdiaphragm
Switching elementmicroswitch
Electrical connectionAMP plugs
Weight150 g
Designed lifetime10 years
Safety class2
Cover screw50 Ncm
Strain relief facility60 Ncm
Diaphragm materialNBR
Silicone-freeyes
Low gas releaseyes
Micro switch standardEN 61058-1
Tested type sampleyes
Production surveillanceyes
Pressure typepositive, negative or differential pressure
Safety chain rolesafety-critical product
all specifications (18) ↓
113.78 EUR
103.44EUR
in stock · 3

incl. 21% VAT · 85.49 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DL2EH-1 air pressure switch (SKU 84444100) is a safety-critical device designed to monitor positive, negative, or differential pressure of non-aggressive gases, air, or flue gases. It features a diaphragm sensing element made of NBR and a microswitch conforming to EN 61058-1. The housing is constructed from glass fibre reinforced PBT plastic with low gas release, and the unit is silicone-free. The pressure range is 0.45 to 2 mbar, and it operates with a designed lifetime of 10 years under specified conditions. Electrical connection is via AMP plugs, and the weight is 150 g. The cover screw torque is 50 Ncm, and the strain relief facility torque is 60 Ncm. It meets safety class 2 and is tested and produced under surveillance according to relevant directives and standards.

Further details

Aging effectlong-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life
Gas Typeair or flue gas, no flammable gases, no aggressive gases
Mediumnon-aggressive gases, air or flue gases
Replacement criteriaupon reaching the end of the designed lifetime, safety-critical products should be replaced

Choosing and fitting

When selecting a replacement pressure switch of this type, verify the required pressure range, electrical connection type (e.g., AMP plugs), and mounting configuration. Ensure the switch is suitable for the medium (non-aggressive gases, air, or flue gas) and that the ambient and medium temperatures are within the specified limits. Check the electrical ratings and safety approvals to match the system requirements. Installation should follow the manufacturer's instructions, including proper torque for cover screws and strain relief.

Signs of failure

Common failure modes for diaphragm-based pressure switches include diaphragm rupture or leakage, leading to loss of pressure sensing or false triggering. Microswitch contacts may wear or stick, causing intermittent or continuous signals. Symptoms on equipment may include burner lockout, failure to start, or erratic operation. Check for physical damage, verify pressure setpoint with a manometer, and test electrical continuity of the switch.

All specifications

Setting range0.45–2 mbar
Body materialglass fibre reinforced PBT plastic
Sensing elementdiaphragm
Switching elementmicroswitch
Electrical connectionAMP plugs
Weight150 g
Designed lifetime10 years
Safety class2
Cover screw50 Ncm
Strain relief facility60 Ncm
Diaphragm materialNBR
Silicone-freeyes
Low gas releaseyes
Micro switch standardEN 61058-1
Tested type sampleyes
Production surveillanceyes
Pressure typepositive, negative or differential pressure
Safety chain rolesafety-critical product

Part numbers

SKU84444100
Additional article624.214.170
ModelDL2EH-1