Key specifications
| Setting range | 0.45–2 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| Sensing element | diaphragm |
| Switching element | microswitch |
| Electrical connection | AMP plugs |
| Weight | 150 g |
| Designed lifetime | 10 years |
| Safety class | 2 |
| Cover screw | 50 Ncm |
| Strain relief facility | 60 Ncm |
| Diaphragm material | NBR |
| Silicone-free | yes |
| Low gas release | yes |
| Micro switch standard | EN 61058-1 |
| Tested type sample | yes |
| Production surveillance | yes |
| Pressure type | positive, negative or differential pressure |
| Safety chain role | safety-critical product |
113.78 EUR
103.44EUR
in stock · 3
incl. 21% VAT · 85.49 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder DL2EH-1 air pressure switch (SKU 84444100) is a safety-critical device designed to monitor positive, negative, or differential pressure of non-aggressive gases, air, or flue gases. It features a diaphragm sensing element made of NBR and a microswitch conforming to EN 61058-1. The housing is constructed from glass fibre reinforced PBT plastic with low gas release, and the unit is silicone-free. The pressure range is 0.45 to 2 mbar, and it operates with a designed lifetime of 10 years under specified conditions. Electrical connection is via AMP plugs, and the weight is 150 g. The cover screw torque is 50 Ncm, and the strain relief facility torque is 60 Ncm. It meets safety class 2 and is tested and produced under surveillance according to relevant directives and standards.
Further details
| Aging effect | long-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life |
|---|---|
| Gas Type | air or flue gas, no flammable gases, no aggressive gases |
| Medium | non-aggressive gases, air or flue gases |
| Replacement criteria | upon reaching the end of the designed lifetime, safety-critical products should be replaced |
Choosing and fitting
When selecting a replacement pressure switch of this type, verify the required pressure range, electrical connection type (e.g., AMP plugs), and mounting configuration. Ensure the switch is suitable for the medium (non-aggressive gases, air, or flue gas) and that the ambient and medium temperatures are within the specified limits. Check the electrical ratings and safety approvals to match the system requirements. Installation should follow the manufacturer's instructions, including proper torque for cover screws and strain relief.
Signs of failure
Common failure modes for diaphragm-based pressure switches include diaphragm rupture or leakage, leading to loss of pressure sensing or false triggering. Microswitch contacts may wear or stick, causing intermittent or continuous signals. Symptoms on equipment may include burner lockout, failure to start, or erratic operation. Check for physical damage, verify pressure setpoint with a manometer, and test electrical continuity of the switch.
All specifications
| Setting range | 0.45–2 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| Sensing element | diaphragm |
| Switching element | microswitch |
| Electrical connection | AMP plugs |
| Weight | 150 g |
| Designed lifetime | 10 years |
| Safety class | 2 |
| Cover screw | 50 Ncm |
| Strain relief facility | 60 Ncm |
| Diaphragm material | NBR |
| Silicone-free | yes |
| Low gas release | yes |
| Micro switch standard | EN 61058-1 |
| Tested type sample | yes |
| Production surveillance | yes |
| Pressure type | positive, negative or differential pressure |
| Safety chain role | safety-critical product |
Part numbers
| SKU | 84444100 |
|---|---|
| Additional article | 624.214.170 |
| Model | DL2EH-1 |