{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Air pressure switch DL3E-1 84444210

SKU 84444210 Model DL3E-1 Brand Kromschroder

Photos

Key specifications

Setting range0.3–3 mbar
Body materialglass fibre reinforced PBT plastic
Sensing elementtempered LSR diaphragm
Switching elementmicroswitch
Operating principlediaphragm pressure switch
Electrical connectionAMP plugs
Weight0.3 g
Designed lifetime10 years
Diaphragm systemtempered LSR diaphragm system
Micro switch standardEN 61058-1
Strain relief torque65 Ncm
Safety classII to VDE 0106-1
Cover screw65 Ncm
StandardsEN 13611 and EN 1854
all specifications (14) ↓
144.52 EUR
131.38EUR
in stock · 5

incl. 21% VAT · 108.58 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DL3E-1 air pressure switch (SKU 84444210) is a diaphragm pressure switch designed to regulate positive, negative, or differential air and flue gas pressures. It features a tempered LSR diaphragm system and a glass fibre reinforced PBT plastic housing. The switch operates within a pressure range of 0.3–3 mbar and includes a microswitch conforming to EN 61058-1. It is safety class II to VDE 0106-1 and has a designed lifetime of 10 years per EN 13611 and EN 1854. Electrical connection is via AMP plugs, and the weight is 0.3 kg.

Further details

Gas typeair or flue gas, no flammable gases, no aggressive gases
Pressure typepositive, negative, or differential air and flue gas pressures
Special design pressure switchcan be used as 'special-design pressure switch'

Choosing and fitting

When selecting a replacement pressure switch of this type, verify the pressure range, electrical connection type, and mounting configuration. Ensure the switch is suitable for the medium (air or flue gas) and that the electrical ratings match the control circuit. Check the physical dimensions and thread or tube connections to fit the existing installation.

Signs of failure

Common failure modes include diaphragm rupture or leakage, leading to loss of pressure sensing and improper burner operation. Symptoms may include burner lockout, failure to start, or unstable flame. Check for visible damage, test the switch with a manometer, and verify electrical continuity.

All specifications

Setting range0.3–3 mbar
Body materialglass fibre reinforced PBT plastic
Sensing elementtempered LSR diaphragm
Switching elementmicroswitch
Operating principlediaphragm pressure switch
Electrical connectionAMP plugs
Weight0.3 g
Designed lifetime10 years
Diaphragm systemtempered LSR diaphragm system
Micro switch standardEN 61058-1
Strain relief torque65 Ncm
Safety classII to VDE 0106-1
Cover screw65 Ncm
StandardsEN 13611 and EN 1854

Part numbers

SKU84444210
Additional article624.214.075
ModelDL3E-1