Kromschroder Air pressure switch DL3K-3 84444608
SKU 84444608
Model DL3K-3
Brand Kromschroder
Photos
Key specifications
| Setting range | 0.2–3 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| Sensing element | tempered LSR diaphragm |
| Switching element | microswitch |
| Electrical connection | screw terminals |
| Weight | 250 g |
| Cover screw | 65 Ncm |
| Strain relief facility | 65 Ncm |
| Designed lifetime | 10 years |
| Diaphragm system | tempered LSR diaphragm system |
| Micro switch standard | EN 61058-1 |
| Safety class | 2 |
| Standards | EN 13611:2015+AC:2016 and EN 1854:2010 |
| Certification | CE-0085AP0466 |
| Tested type sample | matches tested type samples |
| Operating principle | diaphragm pressure switch |
188.32 EUR
171.20EUR
in stock · 2
incl. 21% VAT · 141.49 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder DL3K-3 air pressure switch (SKU 84444608) is a diaphragm pressure switch designed to control positive, negative, or differential air and flue gas pressures. It has an adjusting range of 0.2 to 3 mbar and features a tempered LSR diaphragm system. The housing is made of glass fibre reinforced PBT plastic, and the electrical connection is via screw terminals. The switch weighs 250 g, has a cover screw torque of 65 Ncm, and a designed lifetime of 10 years. It complies with EN 13611:2015+AC:2016 and EN 1854:2010, and carries CE-0085AP0466 certification.
Further details
| Gas Type | air or flue gas, no flammable gases, no aggressive gases |
|---|---|
| Housing With Tube Connection And Hand Wheel | housing with tube connection and hand wheel |
| Pressure Type | positive, negative, or differential air and flue gas pressures |
| Production Surveillance | according to directives 2009/142/EC annex II and regulation (EU) 2016/426 annex III |
| Special Design Pressure Switch | can be used as 'special-design pressure switch' |
Choosing and fitting
When selecting a replacement pressure switch of this type, ensure the pressure range, electrical connection type, and mounting configuration match the original. Check the medium compatibility (air or flue gas) and the maximum temperature limits. The switch should be installed with proper strain relief and the cover screw tightened to the specified torque.
Signs of failure
Common failure modes for diaphragm pressure switches include diaphragm rupture or leakage, leading to loss of pressure sensing. Symptoms may include burner lockout, erratic operation, or failure to detect pressure changes. Check for visible damage to the diaphragm, proper electrical continuity, and correct pressure setpoint adjustment.
All specifications
| Setting range | 0.2–3 mbar |
|---|---|
| Body material | glass fibre reinforced PBT plastic |
| Sensing element | tempered LSR diaphragm |
| Switching element | microswitch |
| Electrical connection | screw terminals |
| Weight | 250 g |
| Cover screw | 65 Ncm |
| Strain relief facility | 65 Ncm |
| Designed lifetime | 10 years |
| Diaphragm system | tempered LSR diaphragm system |
| Micro switch standard | EN 61058-1 |
| Safety class | 2 |
| Standards | EN 13611:2015+AC:2016 and EN 1854:2010 |
| Certification | CE-0085AP0466 |
| Tested type sample | matches tested type samples |
| Operating principle | diaphragm pressure switch |
Part numbers
| SKU | 84444608 |
|---|---|
| Additional article | 624.214.156 |
| Model | DL3K-3 |