{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Air pressure switch DL5AT-2N 84444970

SKU 84444970 Model DL5AT-2N Brand Kromschroder

Photos

no photo yet

Key specifications

Setting range0.5–5 mbar
Connection threadNPT 1/4
Protection class (IP)IP54
Body materialglass fibre reinforced PBT plastic
Conduit thread1/2 NPT conduit
Weight54 g
Cover screw65 Ncm
Strain relief facility65 Ncm
Diaphragm systemtempered LSR diaphragm system
Micro switch standardEN 61058-1
Safety classVDE 0106-1
Pilot lamp colorblue
Scale typeinch and mbar scale
Mediumair or flue gas
StandardsEN 13611:2015+AC:2016 and EN 1854:2010
CertificationCE-0085AP0466
Pressure typepositive, negative, or differential pressure
Production surveillanceongoing production surveillance procedures
Directive 2009/142/ECcompliant
Regulation (EU) 2016/426compliant
all specifications (20) ↓
189.13 EUR
171.94EUR
in stock · 2

incl. 21% VAT · 142.10 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DL5AT-2N air pressure switch (SKU 84444970) is a diaphragm-based pressure switch designed for use with air or flue gas. It operates over a pressure range of 0.5–5 mbar and can sense positive, negative, or differential pressure. The switch features a glass fibre reinforced PBT plastic housing with an NPT 1/4 connection thread and a 1/2 NPT conduit thread. It includes a blue pilot lamp for 110/120 V AC, a micro switch conforming to EN 61058-1, and a tempered LSR diaphragm system. The device weighs 54 g, has a protection class of IP54, and is certified to CE-0085AP0466, complying with EN 13611:2015+AC:2016 and EN 1854:2010.

Further details

Electrical Connectionscrew terminals and 1/2 NPT conduit
Tested type samplecorresponds to the tested type sample

Choosing and fitting

When selecting a replacement pressure switch of this type, verify the pressure range, connection thread size, and electrical ratings (voltage and current) match the original. Ensure the switch is suitable for the medium (air or flue gas) and the required pressure type (positive, negative, or differential). Mounting may involve threaded connections or conduit fittings; check the physical dimensions and conduit thread (e.g., 1/2 NPT) to fit the existing installation. Also confirm the protection class (e.g., IP54) meets the environmental requirements.

Signs of failure

Common failure modes for pressure switches of this kind include diaphragm rupture or leakage, leading to loss of pressure sensing or false triggering. Symptoms may include the burner failing to start, intermittent shutdowns, or the switch not responding to pressure changes. Check for physical damage, contamination, or blockage in the pressure ports, and verify the electrical continuity of the micro switch. If the switch is stuck open or closed, it may prevent proper operation of the burner control system.

All specifications

Setting range0.5–5 mbar
Connection threadNPT 1/4
Protection class (IP)IP54
Body materialglass fibre reinforced PBT plastic
Conduit thread1/2 NPT conduit
Weight54 g
Cover screw65 Ncm
Strain relief facility65 Ncm
Diaphragm systemtempered LSR diaphragm system
Micro switch standardEN 61058-1
Safety classVDE 0106-1
Pilot lamp colorblue
Scale typeinch and mbar scale
Mediumair or flue gas
StandardsEN 13611:2015+AC:2016 and EN 1854:2010
CertificationCE-0085AP0466
Pressure typepositive, negative, or differential pressure
Production surveillanceongoing production surveillance procedures
Directive 2009/142/ECcompliant
Regulation (EU) 2016/426compliant

Part numbers

ModelDL5AT-2N
SKU84444970
Additional article624.214.238