{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Air pressure switch DL8K-3 84444740

SKU 84444740 Model DL8K-3 Brand Kromschroder

Photos

Key specifications

Setting range0.5–8 mbar
Body materialglass fibre reinforced PBT plastic
Sensing elementtempered LSR diaphragm
Switching elementmicro switch
Operating principlemechanical pressure switch
Electrical connectionscrew terminals
Mediumair or flue gas
Weight200 g
Adjusting range0.5–8 mbar
Safety classII
Cover screw65 Ncm
Diaphragm systemtempered LSR diaphragm
Micro switch standardEN 61058-1
Strain relief torque65 Ncm
Pressure typeoverpressure, vacuum and pressure drop
Device typepressure switch
StandardsEN 61058-1
Strain relief facility65 Ncm
Net weight0.0002 kg
Gross weight0.0002 kg
Construction typediaphragm pressure switch
Diaphragm materialLSR
Low gas releaseyes
Component typepressure switch
Adjustment methodhand wheel
all specifications (25) ↓
149.71 EUR
136.10EUR
in stock · 1

incl. 21% VAT · 112.48 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder DL8K-3 is a mechanical diaphragm pressure switch designed for monitoring overpressure, vacuum, and pressure drop in air or flue gas systems. It has an adjusting range of 0.5–8 mbar and features a tempered LSR diaphragm system within a glass fibre reinforced PBT plastic housing. The switch uses a micro switch compliant with EN 61058-1 and connects via screw terminals. It operates within a safety class II rating and weighs 200 g. The cover screw and strain relief facility require a torque of 65 Ncm.

Further details

Gas Typeair or flue gas, no flammable gases, no aggressive gases
Housing Typehousing with tube connection and hand wheel

Choosing and fitting

When selecting a pressure switch of this type, ensure the pressure range and medium compatibility match your system. Verify the electrical connection type (e.g., screw terminals) and the mounting orientation. Check the switch's safety class and any required standards. For installation, torque the cover screw and strain relief to the specified value, typically 65 Ncm.

Signs of failure

Common failure modes for diaphragm pressure switches include diaphragm rupture or leakage, leading to loss of pressure sensing. This may cause the burner or boiler to shut down or fail to start. Micro switch contacts can wear or stick, resulting in erratic operation or no switching. Check for physical damage, contamination, or incorrect adjustment. Verify the switch operation by applying pressure and measuring continuity.

All specifications

Setting range0.5–8 mbar
Body materialglass fibre reinforced PBT plastic
Sensing elementtempered LSR diaphragm
Switching elementmicro switch
Operating principlemechanical pressure switch
Electrical connectionscrew terminals
Mediumair or flue gas
Weight200 g
Adjusting range0.5–8 mbar
Safety classII
Cover screw65 Ncm
Diaphragm systemtempered LSR diaphragm
Micro switch standardEN 61058-1
Strain relief torque65 Ncm
Pressure typeoverpressure, vacuum and pressure drop
Device typepressure switch
StandardsEN 61058-1
Strain relief facility65 Ncm
Net weight0.0002 kg
Gross weight0.0002 kg
Construction typediaphragm pressure switch
Diaphragm materialLSR
Low gas releaseyes
Component typepressure switch
Adjustment methodhand wheel

Part numbers

SKU84444740
Additional article624.214.241
ModelDL8K-3