Honeywell Gas boiler control unit S4560A1008U

SKU S4560A1008U Model S4560A1008 Brand Honeywell

Photos

Key specifications

Cycle typeintermittent
Flame detector typeflame sensor rod
Frequency50 Hz
Ignition typedirect
Applicationatmospheric gas burners
Safety standardEN 298
Supply voltage220–240 V
Fuelgas
TC test period tP2.5 s
Connector typeMolex 3001 multi-edge connector
Behaviour in the event of flame failure during operationrepeats ignition sequence
Flame relay outputyes
Fan supportyes
Internal ignitionno
Lockout typenon-volatile blocking
Maintenance freeyes
Power consumption10 W
Reset button typeexternal or internal reset button
Blocking in absence of etheryes
Safety featureManual reset lockout
Safety time10 s
Time ts10 s
Protection class (IP)IP40
Restart behaviorrepeats ignition sequence
Reset wait time15 s
Blocking during flame simulationyes
Gas valve + GPS connectionyes
Input signal protection from resetyes
Quick launch optionyes
LPG valve supportyes
Maximum thermal relay requiredyes
Shielded ignition cables requiredyes
Length137 mm
Width86 mm
Height49 mm
EN 298 complianceyes
Application typeatmospheric gas burners
Flame monitoringflame sensor rod
Waiting time0 s
Mounting hole diameter4.5 mm
Spark terminal size2.8 mm
Flame extinguisher tip size6.3 mm
External fuseyes
Rigid lockingyes
High temperature effectshortens service life
Gas pressure monitoringyes
TTB relay reset requiredyes
all specifications (47) ↓
419.27 EUR
381.15EUR
in stock · 1

incl. 21% VAT · 315.00 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Honeywell S4560A1008U is a gas boiler control unit for atmospheric gas burners. It operates in intermittent cycle mode with direct ignition and flame monitoring via a sensor rod. The unit conforms to EN 298 and features a non-volatile lockout with manual reset. It operates at 220–240 V, 50 Hz, with a power consumption of 10 W and a safety time of 10 s. The control box has a Molex 3001 multi-edge connector, supports a fan, and is rated IP40. It is maintenance-free and requires external fuses and a thermal relay.

Choosing and fitting

Control boxes of this type are selected by matching the supply voltage, frequency, safety time, and connector configuration of the existing installation. Before ordering, compare the mounting dimensions and terminal sizes with the original unit. During installation, provide external fuses for safety and place the controller away from heat and radiation. The overall enclosure protection must be at least IP40, and spark ignition cables must be shielded. These controllers have no user-serviceable parts; do not attempt internal repairs.

Signs of failure

Typical failure of these control units is a lockout when the flame is not detected within the safety time, often caused by a dirty or misaligned flame sensor rod. If the flame goes out during operation, the unit repeats the ignition sequence. Lockout is non-volatile and requires manual reset via the external or internal reset button. If the first reset fails, wait at least 15 seconds before again attempting reset.

All specifications

Cycle typeintermittent
Flame detector typeflame sensor rod
Frequency50 Hz
Ignition typedirect
Applicationatmospheric gas burners
Safety standardEN 298
Supply voltage220–240 V
Fuelgas
TC test period tP2.5 s
Connector typeMolex 3001 multi-edge connector
Behaviour in the event of flame failure during operationrepeats ignition sequence
Flame relay outputyes
Fan supportyes
Internal ignitionno
Lockout typenon-volatile blocking
Maintenance freeyes
Power consumption10 W
Reset button typeexternal or internal reset button
Blocking in absence of etheryes
Safety featureManual reset lockout
Safety time10 s
Time ts10 s
Protection class (IP)IP40
Restart behaviorrepeats ignition sequence
Reset wait time15 s
Blocking during flame simulationyes
Gas valve + GPS connectionyes
Input signal protection from resetyes
Quick launch optionyes
LPG valve supportyes
Maximum thermal relay requiredyes
Shielded ignition cables requiredyes
Length137 mm
Width86 mm
Height49 mm
EN 298 complianceyes
Application typeatmospheric gas burners
Flame monitoringflame sensor rod
Waiting time0 s
Mounting hole diameter4.5 mm
Spark terminal size2.8 mm
Flame extinguisher tip size6.3 mm
External fuseyes
Rigid lockingyes
High temperature effectshortens service life
Gas pressure monitoringyes
TTB relay reset requiredyes

Part numbers

SKUS4560A1008U
Additional article534.412.141
ModelS4560A1008
Type designationS4560B1089U