Kromschroder Burner control unit IFD 258-10/2Q 84621460
SKU 84621460
Model IFD 258-10/2Q
Brand Kromschroder
Photos
no photo yet
Key specifications
| Supply voltage | 120 V |
|---|---|
| Safety time | 2 s |
| Flame detector type | Ionization or UV |
| Protection class (IP) | IP54 |
| Ambient temperature | -20–60 °C |
| Weight | 682 g |
| Certification | EN 746-2 |
| Fuel | Gas |
| Safety standard | EN 60730 |
| Air supply | Atmospheric / forced draught |
| Flame detection methods supported | Ionization, UV |
| Installation position | any |
| Ignition type | Direct ignition |
| Sensor voltage | 230 |
| Overvoltage category | III |
| Relative humidity | No condensation permitted |
| Enclosure standard | IEC 529 |
| Cable gland | M16 |
| Frequency range | 50–60 Hz |
| Power consumption | 9 W |
| Reset button operating cycles | 1000 cycles |
| Mains button operating cycles | 1000 cycles |
| Max. number of operating cycles | 250000 |
| Behaviour in the event of flame failure during operation | Immediate fault lock-out or restart |
| Operation type | Continuous operation |
| Frequent cycling suitability | Suitable for frequent cycling |
| Supported burner modes | Modulating and stage-controlled |
| Electronic design | Fully electronic |
| Multi-burner control | Yes |
| Net weight | 0.682 kg |
1016.75 EUR
924.32EUR
in stock · 1
incl. 21% VAT · 763.90 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This burner control unit is designed for direct ignition and supervision of gas burners. It supports both ionization and UV flame detection methods. The unit operates in continuous mode and suits frequent cycling, as well as modulating and stage-controlled burners. Its fully electronic design enables use with atmospheric and forced draught burners, and it can be applied in multi-burner systems where a central control handles pre-purge and monitoring. Technical features include a supply voltage of 120 V, power consumption of 9 W, safety time of 2 s, and ambient temperature range of -20 to 60 °C.
Further details
| Cable gland | M16 |
|---|---|
| Display | Program status and flame signal intensity |
| Enclosure | IP 54 pursuant to IEC 529 |
| Installation position | any |
| Mains voltage | 120 V AC, 50/60 Hz |
| Power consumption | approx. 9 VA |
| Relative humidity | no condensation permitted |
| Sensor current | > 2 µA |
| Sensor voltage | approx. 230 V AC |
All specifications
| Supply voltage | 120 V |
|---|---|
| Safety time | 2 s |
| Flame detector type | Ionization or UV |
| Protection class (IP) | IP54 |
| Ambient temperature | -20–60 °C |
| Weight | 682 g |
| Certification | EN 746-2 |
| Fuel | Gas |
| Safety standard | EN 60730 |
| Air supply | Atmospheric / forced draught |
| Flame detection methods supported | Ionization, UV |
| Installation position | any |
| Ignition type | Direct ignition |
| Sensor voltage | 230 |
| Overvoltage category | III |
| Relative humidity | No condensation permitted |
| Enclosure standard | IEC 529 |
| Cable gland | M16 |
| Frequency range | 50–60 Hz |
| Power consumption | 9 W |
| Reset button operating cycles | 1000 cycles |
| Mains button operating cycles | 1000 cycles |
| Max. number of operating cycles | 250000 |
| Behaviour in the event of flame failure during operation | Immediate fault lock-out or restart |
| Operation type | Continuous operation |
| Frequent cycling suitability | Suitable for frequent cycling |
| Supported burner modes | Modulating and stage-controlled |
| Electronic design | Fully electronic |
| Multi-burner control | Yes |
| Net weight | 0.682 kg |
Part numbers
| SKU | 84621460 |
|---|---|
| Additional article | 624.103.163 |
| Model | IFD 258-10/2Q |