{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Cofi High-voltage ignition transformer TRG1020C

SKU TRG1020C Brand Cofi

Photos

Key specifications

Supply voltage230 V
Secondary voltage5 kV
Poles / outlets2
Length110 mm
Width90 mm
Height70 mm
Ignition cable insulationsilicone-insulated
Dimensions110 x 90 x 70 mm
Compact designcompact
Reliabilityhigh reliability
External package dimensions (LxWxH)190 x 130 x 105 mm
Package Length190 mm
Number of outputs2
High voltage outputs2
Compact sizecompact
Package width130 mm
Package depth105 mm
Current1 A
Output voltage frequency2 kHz
MOQ5 pcs
Operating phaseignition period
Duty cycleenergised only during ignition period
Net weight2.725 kg
Gross weight2.8 kg
Frequency50 Hz
all specifications (25) ↓
148.12 EUR
134.65EUR
in stock · 3

incl. 21% VAT · 111.28 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Cofi TRG1020C is a high-voltage ignition transformer designed to generate a spark in automatic ignition systems for gas and liquid fuel burners. It operates with a supply voltage of 230 V at 50 Hz, drawing 1 A, and provides two high-voltage outputs of 5 kV each at a frequency of 2 kHz. The transformer is compact, measuring 110 x 90 x 70 mm, with a net weight of 2.725 kg. It is energised only during the ignition period, as controlled by the burner control box, ensuring stable and safe equipment startup.

Further details

Application areagas burners, liquid fuel burners, boiler equipment, industrial heat generators, automatic ignition systems
Application scopegas burners, liquid fuel burners, boiler equipment, industrial heat generators, automatic ignition systems
Cable condition checkinspect cable and connections when replacing
Energizationenergised only during the ignition period

Choosing and fitting

When selecting a replacement ignition transformer of this type, ensure the primary voltage matches the burner control supply (commonly 230 V, but 110 V or 24 V variants exist). The secondary voltage and current must be compatible with the electrode gap and burner design. Check the duty cycle, as some burners require longer ignition periods. Verify that mounting dimensions, terminal layout, and cable connector pattern fit the existing bracket and wiring. The high-voltage ignition cable should be silicone-insulated; inspect it for hardening or cracks before installation.

Signs of failure

Typical failures of ignition transformers include internal short circuits, open windings, or insulation breakdown, leading to weak or no spark. The burner may fail to ignite, causing the control box to lock out after repeated attempts. Check for visible damage, overheating, or a cracked high-voltage cable that can leak spark to ground. Measure primary and secondary voltages with a multimeter to confirm the transformer is functioning within specifications.

All specifications

Supply voltage230 V
Secondary voltage5 kV
Poles / outlets2
Length110 mm
Width90 mm
Height70 mm
Ignition cable insulationsilicone-insulated
Dimensions110 x 90 x 70 mm
Compact designcompact
Reliabilityhigh reliability
External package dimensions (LxWxH)190 x 130 x 105 mm
Package Length190 mm
Number of outputs2
High voltage outputs2
Compact sizecompact
Package width130 mm
Package depth105 mm
Current1 A
Output voltage frequency2 kHz
MOQ5 pcs
Operating phaseignition period
Duty cycleenergised only during ignition period
Net weight2.725 kg
Gross weight2.8 kg
Frequency50 Hz

Part numbers

SKUTRG1020C
Additional article309.820.043