Cofi Ignition transformer TRS830P/6

SKU TRS830P/6 Brand Cofi

Photos

Key specifications

Supply voltage230 V
Secondary voltage8 kV
Poles / outlets1
Length520 mm
Width110 mm
Height66 mm
Construction typetraditional electromagnetic, with grounded pole
Ignition cable connectorstandard ø 4 mm
CertificationCEI EN 61558-2-3
Epoxy pottingyes
Protection against moisture, vibration, overheatingyes
Peak voltage11 kV
Primary current1.5–1.6 A
Ignition cable insulationsilicone-insulated
Secondary current30 mA
Duty cycle25% ed (within 4 minutes)
Net weight1.94 kg
Gross weight2.015 kg
Frequency50 Hz
Country of originItaly
all specifications (20) ↓
114.20 EUR
103.82EUR
in stock · 2

incl. 21% VAT · 85.80 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Cofi TRS830P/6 is an ignition transformer designed for use in liquid fuel burners, generating a high-voltage spark to ignite the fuel-air mixture. It operates on a 230 V, 50 Hz supply, drawing a primary current of 1.5–1.6 A, and produces a secondary voltage of 8 kV with a peak of 11 kV and a secondary current of 30 mA. The transformer has a duty cycle of 25% ED within a 4-minute period and features a traditional electromagnetic construction with a grounded pole. It is epoxy-potted for protection against moisture, vibration, and overheating, and includes a standard ø 4 mm ignition cable connector. The unit measures 520 x 110 x 66 mm, weighs 1.94 kg net, and is certified to CEI EN 61558-2-3.

Further details

Advantagesenhanced powerful spark, high reliability, excellent compatibility, long service life, easy installation
Application scopereliable ignition in small and medium power liquid fuel burners running on diesel, fuel oil and waste oil
Compatible Burnersriello, ecoflam, fbr, baltur, lamborghini, bentone, giersch, weishaupt
Energizationenergised only during the ignition period
Functiongenerate high-voltage spark for burner ignition
Maintenance requirementcheck ignition cables condition before replacing transformer
Operating principlesteps up the mains voltage to a level that produces an arc across the ignition electrode gap

Choosing and fitting

When selecting an ignition transformer of this type, verify that the primary voltage and frequency match the burner's supply, and that the secondary voltage and current are suitable for the electrode gap and burner design. The duty cycle must align with the ignition sequence of the burner control. Check the physical mounting dimensions, terminal type, and cable connector pattern to ensure compatibility with the existing setup. Before ordering, compare the transformer's specifications with the original part's data, and inspect the ignition cables for damage, as hardened or cracked insulation can cause spark leakage and mimic transformer failure.

Signs of failure

Common failure modes for ignition transformers include internal short circuits, open windings, or insulation breakdown, which can result in no spark, weak spark, or intermittent ignition. The burner may fail to light, lock out, or cycle repeatedly. Check for visible signs of overheating, such as discoloration or a burnt smell, and test the primary and secondary circuits with appropriate instruments. Also inspect the high-voltage cable and electrode connections for wear or corrosion, as these can cause similar symptoms.

Fits equipment

Riello Ecoflam FBR Baltur Lamborghini Bentone Giersch Weishaupt

All specifications

Supply voltage230 V
Secondary voltage8 kV
Poles / outlets1
Length520 mm
Width110 mm
Height66 mm
Construction typetraditional electromagnetic, with grounded pole
Ignition cable connectorstandard ø 4 mm
CertificationCEI EN 61558-2-3
Epoxy pottingyes
Protection against moisture, vibration, overheatingyes
Peak voltage11 kV
Primary current1.5–1.6 A
Ignition cable insulationsilicone-insulated
Secondary current30 mA
Duty cycle25% ed (within 4 minutes)
Net weight1.94 kg
Gross weight2.015 kg
Frequency50 Hz
Country of originItaly

Part numbers

SKUTRS830P/6
Additional article309.820.088