Siemens UV cell 450211310
SKU 450211310
Brand Siemens
Photos
234.87 EUR
213.52EUR
in stock · 2
incl. 21% VAT · 176.46 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This UV cell from Siemens, SKU 450211310, belongs to the sensor components category. It is used for flame supervision in oil-fired or industrial gas burners where an ionisation electrode is not suitable. The cell detects the ultraviolet radiation emitted by the flame and sends a signal to the burner control through a shielded cable to confirm that ignition has occurred and that the flame remains present during operation. It fits a Landis & Gyr AGR450211310.
Further details
| Application | used for flame supervision in oil-fired or industrial gas burners |
|---|---|
| Operating Principle | detects ultraviolet radiation emitted by the flame |
Choosing and fitting
UV cells of this kind are selected by comparing the required sensitivity (minimum UV intensity to produce a flame signal) and spectral range with the burner type and fuel. The electrical supply voltage, normally a pulsed DC from the control, and the connector type must also be compatible with the existing burner control. Some cells have an integral amplifier; others are passive. A UV cell is usually mounted in a holder that sights through a port or the blast tube into the combustion chamber; before ordering, check that the lens is clean, the gasket seals properly, and that the manufacturer's part number cross-reference matches the control. Observe wiring orientation because some circuits are polarity-sensitive.
Signs of failure
When a UV cell of this type loses its flame signal—for instance because the lens is fouled by soot or an oil film, or the gasket leaks flue gas—the burner control will not confirm the flame and initiates a lockout within the safety time. A cell that views hot refractory or only a pilot flame instead of the main flame zone may deliver a false signal or fail to respond to flame loss. In polarity-sensitive circuits, reversed wiring causes immediate lockout. Usually these failures are detected by checking the lens, gasket, mounting position and wiring orientation before replacing an otherwise functional cell.
Fits equipment
Landis & Gyr AGR450211310
All specifications
| Electrical connection | shielded cable to burner control |
|---|
Part numbers
| SKU | 450211310 |
|---|---|
| Additional article | 920.973.005 |